1.0.1 This code is formulated with a view to preventing and reducing building fire hazards and safeguarding people's life and property.
1.0.2 This code shall be applicable to the construction, extension and renovation of the buildings specified as follows:
1 Residential buildings of 9 stories or below (including residential buildings with commercial service facilities);
2 Public buildings not over 24m high;
3 Single story public buildings over 24m high;
4 Underground and semi-underground buildings (including basement and semi-basement of the building);
5 Factory building;
6 Storage;
7 Storage tank (tank farm) for Class A, B and C liquid;
8 Storage tank (tank farm) for combustible and combustion-supporting gas;
9 Combustible stackyard;
10 City traffic tunnel.
Note: 1 Measurement of the building height: When the roof is slope, the height of the building shall be measured from the design ground level outside the building to the eaves; when the roof is flat (including the flat roof with parapet wall), the height of the building shall be measured from the design ground level outside of the building to the surface of the roof; when the building has various roof shapes, the height of the building shall be measured respectively with the same measurement method and take the greatest value. The sticking out constructions such as observation tower, cooling tower, water tank room, microwave antenna room or equipment, elevator machine room, air and smoke exhaust fan room, staircase exit etc. on the roof may not be counted in the building height.
2 Measurement of the building stones: The basement and semi-basement with its top slab not more than 1.5m high above the design ground level outside of the building, the bicycle storage space, storage and open space not more than 2.2m high at the lower part of the building, and the local equipment room, staircase etc. above the roof may not be counted in the stories. The apartment on the top of the building with two stories as one unit can be considered as one story. The two-story apartment not on the top of the building and the apartment on the top of the building with more than two stories as one unit shall be counted in the stories.
1.0.3 This code is not applicable to the fire protection design of explosive plants (storage) and firecrackers work shops (storage).
If there are current national standards for the fire protection design of civil air defense works, oil and gas installations, petrochemical plants, thermal power plants or transformer substations, it should meet the special requirements of those standards.
1.0.4 The design of building fire protection shall be consistent with the relevant national policies, and the designer shall consider the overall situation to achieve the purpose of ensuring safety, serviceability, technical superiority and economy.
1.0.5 The design of building fire protection shall comply with the stipulation of this code and it shall furthermore comply with the relevant current national codes.
1 General principles 1
2 Terminology 3
3 Factory buildings (storages) 6
3.1 Classification of fire hazards 6
3.2 Fire resistance class of factory buildings (storages) and fire resistance rating of its components 8
3.3 Fire resistance class, number of stories, occupied area and plane arrangement of factory buildings (storages) 10
3.4 Fire separation distance for factory building 16
3.5 Fire separation distance for storage 20
3.6 Explosion prevention of factory buildings (storages) 23
3.7 Safe evacuation in factory buildings 25
3.8 Safe evacuation in storages 27
4 Class A, B, C liquid, gas tank (tank farm) and combustible stackyard 29
4.1 General requirements 29
4.2 Fire separation distance for Class A, B, C liquid tank (tank farm) 29
4.3 Fire separation distance between combustible and combustion-supporting gas tanks (tank farms) 34
4.4 Fire separation distance for LPG tank (tank farm) 37
4.5 Fire separation distance of combustible material stackyard 40
5 Civil buildings 42
5.1 Fire resistance class, number of stories, and building area of civil buildings 42
5.2 Fire separation distance of civil buildings 46
5.3 Safe evacuation in civil buildings 48
5.4 Other requirements 55
8 Fire alarm devices shall be installed. 56
4 Fire alarm devices shall be installed. 56
5.5 Timber civil buildings 57
Table 5.5.2 Stories, length and area of timber-structured buildings 58
6 Fire fighting vehicle access 60
7 Building structure 62
7.1 Fire wall 62
7.2 Building component and conduit shaft 63
7.3 Roof, blind ceiling and building gap 65
7.4 Staircase, stairs and door 65
7.5 Fire door and fire roller shutter 69
7.6 Crossover, trestle and pipe trench 69
8 Fire water supply and fire extinguishing facility 71
8.1 General requirements 71
8.2 Outdoor fire fighting water amount, water supply pipe and fire hydrant 72
8.3 The setting places of indoor fire hydrants etc. 79
8.4 Amount of water required by indoor fire fighting and water supply piping, fire hydrant and reservoir 80
8.5 The places where automatic fire extinguishing system is installed 85
8.6 Fire water pool and fire pump room 87
9 Smoke control and smoke exhaust 91
9.1 General requirements 91
9.2 Natural smoke exhaust 92
9.3 Mechanical smoke control 92
9.4 Mechanical smoke exhaust 94
10 Heating, ventilating and air conditioning 97
10.1 General requirements 97
10.2 Heating 97
10.3 Ventilating and air conditioning 98
11 Electric system 102
11.1 Fire protection power supply and distribution 102
11.2 Power line and electrical equipment 103
11.3 Emergency lighting and evacuation indicating sign 104
11.4 Automatic fire alarm system and fire control room 106
12 City traffic tunnel 108
12.1 General requirements 108
12.2 Fire fighting water supply and fire extinguishing equipment 109
12.3 Ventilating and smoke exhaust system 111
12.4 Automatic fire alarm system 111
12.5 Power supply and the other requirements 112
Explanation of wording in this code 114