2026-6-24 216.73.216.135
Code of China Chinese Classification Professional Classification ICS Classification Latest News Value-added Services

Position: Chinese Standard in English/GB/T 47438.4-2026
GB/T 47438.4-2026   Special requirements for fire alarm and evacuation in hazardous chemicals workplace—Part 4: Portable display devices of alarm information (English)
Standard No.: GB/T 47438.4-2026 Status:to be valid remind me the status change

Email:

Target Language:English File Format:PDF
Word Count: 10000 words Translation Price(USD):300.0 remind me the price change

Email:

Implemented on:2027-5-1 Delivery: via email in 1~5 business day

→ → →

,,2027-5-1,E767B4E9067DD5701778135039515
Standard No.: GB/T 47438.4-2026
English Name: Special requirements for fire alarm and evacuation in hazardous chemicals workplace—Part 4: Portable display devices of alarm information
Chinese Name: 危险化学品作业场所火灾报警与避难逃生特殊要求 第4部分:便携式报警信息显示装置
Professional Classification: GB    National Standard
Source Content Issued by: SAMR, SAC
Issued on: 2026-04-30
Implemented on: 2027-5-1
Status: to be valid
Target Language: English
File Format: PDF
Word Count: 10000 words
Translation Price(USD): 300.0
Delivery: via email in 1~5 business day
GB/T 47438.4-2026 Special requirements for fire alarm and evacuation in hazardous chemicals workplace—Part 4: Portable display devices of alarm information English, Anglais, Englisch, Inglés, えいご This is a draft translation for reference among interesting stakeholders. The finalized translation (passing through draft translation, self-check, revision and verification) will be delivered upon being ordered. ICS CCS National Standard of the People's Republic of China ‌GB/T 47438.4-2026 Special requirements for fire alarm and evacuation in hazardous chemicals workplace - Part 4: Portable display devices of alarm information 危险化学品作业场所火灾报警与避难逃生特殊要求 第4部分:便携式报警信息显示装置 Issue date: 2026-03-31 Implementation date: 2026-10-01 Issued by the General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China the Standardization Administration of the People's Republic of China Contents Foreword Introduction 1 Scope 2 Normative References 3 Terms and Definitions 4 Classification 5 Technical Requirements 5.1 General Requirements 5.2 Basic Functions 5.3 Battery Performance 5.4 Electromagnetic Compatibility Performance 5.5 Climatic Environmental Endurance 5.6 Mechanical Environmental Endurance 5.7 Enclosure Protection Performance 6 Test Methods 6.1 Test Procedure 6.2 Basic Function Test 6.3 Battery Performance Test 6.4 Electrostatic Discharge Immunity Test 6.5 Radiated, RadioFrequency, Electromagnetic Field Immunity Test 6.6 High Temperature (Operating) Test 6.7 Low Temperature (Operating) Test 6.8 Damp Heat, Cyclic (Endurance) Test 6.9 Vibration (Sinusoidal) (Operating) Test 6.10 Vibration (Sinusoidal) (Endurance) Test 6.11 Shock Test 6.12 Enclosure Protection Rating Test 7 Inspection Rules 7.1 Factory Inspection 7.2 Type Inspection 8 Marking 8.1 General Requirements 8.2 Product Marking 8.3 Quality Inspection Marking Special requirements for fire alarm and refuge escape in hazardous chemical workplaces — Part 4: Portable display devices of alarm information 1 Scope This document defines the terms for portable display devices of alarm information, specifies the classification, technical requirements, inspection rules and marking, and describes the corresponding test methods. This document applies to the design, manufacture and inspection of portable display devices of alarm information used in hazardous chemical workplaces. NOTE: Where no confusion is caused, “portable display devices of alarm information” in this document is referred to simply as “display devices”. 2 Normative References The contents of the following documents constitute indispensable provisions of this document through normative references. For dated references, only the edition cited applies. For undated references, the latest edition (including any amendments) applies. GB/T 4208—2017 Degrees of protection provided by enclosure (IP code) GB/T 9969 General principles for instruction manual of industrial products GB 12978 Inspection rules for fire electronic products GB/T 16838 Environmental test methods and severities for fire electronic products GB/T 17626.2 Electromagnetic compatibility — Testing and measurement techniques — Electrostatic discharge immunity test GB/T 17626.3 Electromagnetic compatibility — Testing and measurement techniques — Part 3: Radiated, radiofrequency, electromagnetic field immunity test 3 Terms and definitions The following terms and definitions apply to this document. 3.1 portable display devices of alarm information Portable devices that access terminal devices for fire alarm and refuge escape via wireless communication technology, and send information such as fire alarms, gas leak alarms, equipment faults and emergency evacuation to personnel at the scene. NOTE: Terminal devices include, but are not limited to, fire alarm control units, fire linkage control units, graphic display devices for fire control rooms, emergency lighting control units, combustible gas alarm control units and other such devices. 3.2 continuous positioning type display devices Display devices that have personnel positioning capability and can send user location information to terminal devices throughout the entire area of the workplace. 3.3 anchor positioning type display devices Display devices that have personnel positioning capability and can send information indicating the area where the user is located to terminal devices when the user is within a specified area of the workplace. 4 Classification According to the positioning method used for the product‘s positioning function, display devices can be classified as: a) Continuous positioning type; b) Anchor positioning type. 5 Technical requirements 5.1 General requirements 5.1.1 The surface of the display device shall be free from corrosion, coating peeling and blistering, and shall have no obvious scratches, cracks, burrs or other mechanical damage. Fastening parts shall not be loose. 5.1.2 The mass of the display device should not be greater than 1 kg. The display device shall be equipped with accessories such as lanyards or wrist straps for easy carrying. The accessories shall be able to withstand a tensile force of not less than 20 N between the accessory and the device body. 5.1.3 The display device shall be powered by an internal battery and shall not have the function of supplying power to other equipment. Display devices using disposable replaceable batteries shall have a battery installation structure that prevents reverse polarity connection. 5.1.4 When the display device uses indicator lights to indicate its operating status and alarm information, the normal operating status indicator light shall be green, the fault alarm information and communication fault indicator light shall be yellow, and the fire alarm, combustible gas alarm information and emergency evacuation information indicator light shall be red. 5.1.5 When the display device uses a display screen to indicate its operating status and alarm information, the various types of information shall be displayed using text, symbols or a combination thereof. 5.1.6 Under ambient illumination conditions of 100 lx to 500 lx, the status of the indicator lights and the information on the display screen shall be clearly visible at a distance of 1 m within a 22.5° viewing angle directly in front of the device. 5.1.7 The display device shall have an audible and visual alarm function, and shall emit an alert tone when an alarm message is received. Under ambient sound pressure level (Aweighted) conditions not exceeding 50 dB, the peak sound pressure level (Aweighted) of the acoustic signal of the display device at a distance of 1 m directly in front of the device shall be not less than 60 dB and not greater than 105 dB. When the display device emits an acoustic signal, it shall simultaneously emit a vibration alert. The display device shall have a manual silencing function. When a manual silencing operation is performed, the vibration alert shall also stop simultaneously. 5.1.8 The display device shall have a manual selfcheck or poweron selfcheck function to check the functionality of its indicator lights, display screen and audible/visual components. 5.1.9 The display device shall have an internal timer or be capable of automatically adjusting the clock via a wireless communication network. The daily timing error of the internal timer shall not be greater than ±0.5 s, and the operation of the internal timer shall not be affected by the operating status of the display device. 5.1.10 The maximum communication distance between the display device and a terminal device should not be less than 1000 m, and the maximum communication distance between the display device and a relay device should not be less than 200 m. 5.1.11 When the display device has a positioning function, the positioning error for continuous positioning type display devices intended for outdoor use only should not be greater than 10 m, and for continuous positioning type display devices intended for indoor use, the positioning error should not be greater than 5 m; the positioning error for anchor positioning type display devices intended for outdoor use only should not be greater than 50 m, and for anchor positioning type display devices intended for indoor use, the positioning error should not be greater than 20 m. 5.1.12 When the display device has a remote measurement function, the maximum effective distance for the display device to complete the checkin function interaction with the remote measurement point should not be greater than 5 m. 5.1.13 The display device shall have complete packaging at the time of product delivery. The packaging shall contain a quality inspection certificate and a Chinese instruction manual.
Code of China
Standard
GB/T 47438.4-2026  Special requirements for fire alarm and evacuation in hazardous chemicals workplace—Part 4: Portable display devices of alarm information (English)
Standard No.GB/T 47438.4-2026
Statusto be valid
LanguageEnglish
File FormatPDF
Word Count10000 words
Translation Price(USD)300.0
Implemented on2027-5-1
Deliveryvia email in 1~5 business day
Detail of GB/T 47438.4-2026
Standard No.
GB/T 47438.4-2026
English Name
Special requirements for fire alarm and evacuation in hazardous chemicals workplace—Part 4: Portable display devices of alarm information
Chinese Name
危险化学品作业场所火灾报警与避难逃生特殊要求 第4部分:便携式报警信息显示装置
Chinese Classification
Professional Classification
GB
ICS Classification
Issued by
SAMR, SAC
Issued on
2026-04-30
Implemented on
2027-5-1
Status
to be valid
Superseded by
Superseded on
Abolished on
Superseding
Language
English
File Format
PDF
Word Count
10000 words
Translation Price(USD)
300.0
Keywords
GB/T 47438.4-2026, GB 47438.4-2026, GBT 47438.4-2026, GB/T47438.4-2026, GB/T 47438.4, GB/T47438.4, GB47438.4-2026, GB 47438.4, GB47438.4, GBT47438.4-2026, GBT 47438.4, GBT47438.4
Introduction of GB/T 47438.4-2026
GB/T 47438.4-2026 Special requirements for fire alarm and evacuation in hazardous chemicals workplace—Part 4: Portable display devices of alarm information English, Anglais, Englisch, Inglés, えいご This is a draft translation for reference among interesting stakeholders. The finalized translation (passing through draft translation, self-check, revision and verification) will be delivered upon being ordered. ICS CCS National Standard of the People's Republic of China ‌GB/T 47438.4-2026 Special requirements for fire alarm and evacuation in hazardous chemicals workplace - Part 4: Portable display devices of alarm information 危险化学品作业场所火灾报警与避难逃生特殊要求 第4部分:便携式报警信息显示装置 Issue date: 2026-03-31 Implementation date: 2026-10-01 Issued by the General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China the Standardization Administration of the People's Republic of China Contents Foreword Introduction 1 Scope 2 Normative References 3 Terms and Definitions 4 Classification 5 Technical Requirements 5.1 General Requirements 5.2 Basic Functions 5.3 Battery Performance 5.4 Electromagnetic Compatibility Performance 5.5 Climatic Environmental Endurance 5.6 Mechanical Environmental Endurance 5.7 Enclosure Protection Performance 6 Test Methods 6.1 Test Procedure 6.2 Basic Function Test 6.3 Battery Performance Test 6.4 Electrostatic Discharge Immunity Test 6.5 Radiated, RadioFrequency, Electromagnetic Field Immunity Test 6.6 High Temperature (Operating) Test 6.7 Low Temperature (Operating) Test 6.8 Damp Heat, Cyclic (Endurance) Test 6.9 Vibration (Sinusoidal) (Operating) Test 6.10 Vibration (Sinusoidal) (Endurance) Test 6.11 Shock Test 6.12 Enclosure Protection Rating Test 7 Inspection Rules 7.1 Factory Inspection 7.2 Type Inspection 8 Marking 8.1 General Requirements 8.2 Product Marking 8.3 Quality Inspection Marking Special requirements for fire alarm and refuge escape in hazardous chemical workplaces — Part 4: Portable display devices of alarm information 1 Scope This document defines the terms for portable display devices of alarm information, specifies the classification, technical requirements, inspection rules and marking, and describes the corresponding test methods. This document applies to the design, manufacture and inspection of portable display devices of alarm information used in hazardous chemical workplaces. NOTE: Where no confusion is caused, “portable display devices of alarm information” in this document is referred to simply as “display devices”. 2 Normative References The contents of the following documents constitute indispensable provisions of this document through normative references. For dated references, only the edition cited applies. For undated references, the latest edition (including any amendments) applies. GB/T 4208—2017 Degrees of protection provided by enclosure (IP code) GB/T 9969 General principles for instruction manual of industrial products GB 12978 Inspection rules for fire electronic products GB/T 16838 Environmental test methods and severities for fire electronic products GB/T 17626.2 Electromagnetic compatibility — Testing and measurement techniques — Electrostatic discharge immunity test GB/T 17626.3 Electromagnetic compatibility — Testing and measurement techniques — Part 3: Radiated, radiofrequency, electromagnetic field immunity test 3 Terms and definitions The following terms and definitions apply to this document. 3.1 portable display devices of alarm information Portable devices that access terminal devices for fire alarm and refuge escape via wireless communication technology, and send information such as fire alarms, gas leak alarms, equipment faults and emergency evacuation to personnel at the scene. NOTE: Terminal devices include, but are not limited to, fire alarm control units, fire linkage control units, graphic display devices for fire control rooms, emergency lighting control units, combustible gas alarm control units and other such devices. 3.2 continuous positioning type display devices Display devices that have personnel positioning capability and can send user location information to terminal devices throughout the entire area of the workplace. 3.3 anchor positioning type display devices Display devices that have personnel positioning capability and can send information indicating the area where the user is located to terminal devices when the user is within a specified area of the workplace. 4 Classification According to the positioning method used for the product‘s positioning function, display devices can be classified as: a) Continuous positioning type; b) Anchor positioning type. 5 Technical requirements 5.1 General requirements 5.1.1 The surface of the display device shall be free from corrosion, coating peeling and blistering, and shall have no obvious scratches, cracks, burrs or other mechanical damage. Fastening parts shall not be loose. 5.1.2 The mass of the display device should not be greater than 1 kg. The display device shall be equipped with accessories such as lanyards or wrist straps for easy carrying. The accessories shall be able to withstand a tensile force of not less than 20 N between the accessory and the device body. 5.1.3 The display device shall be powered by an internal battery and shall not have the function of supplying power to other equipment. Display devices using disposable replaceable batteries shall have a battery installation structure that prevents reverse polarity connection. 5.1.4 When the display device uses indicator lights to indicate its operating status and alarm information, the normal operating status indicator light shall be green, the fault alarm information and communication fault indicator light shall be yellow, and the fire alarm, combustible gas alarm information and emergency evacuation information indicator light shall be red. 5.1.5 When the display device uses a display screen to indicate its operating status and alarm information, the various types of information shall be displayed using text, symbols or a combination thereof. 5.1.6 Under ambient illumination conditions of 100 lx to 500 lx, the status of the indicator lights and the information on the display screen shall be clearly visible at a distance of 1 m within a 22.5° viewing angle directly in front of the device. 5.1.7 The display device shall have an audible and visual alarm function, and shall emit an alert tone when an alarm message is received. Under ambient sound pressure level (Aweighted) conditions not exceeding 50 dB, the peak sound pressure level (Aweighted) of the acoustic signal of the display device at a distance of 1 m directly in front of the device shall be not less than 60 dB and not greater than 105 dB. When the display device emits an acoustic signal, it shall simultaneously emit a vibration alert. The display device shall have a manual silencing function. When a manual silencing operation is performed, the vibration alert shall also stop simultaneously. 5.1.8 The display device shall have a manual selfcheck or poweron selfcheck function to check the functionality of its indicator lights, display screen and audible/visual components. 5.1.9 The display device shall have an internal timer or be capable of automatically adjusting the clock via a wireless communication network. The daily timing error of the internal timer shall not be greater than ±0.5 s, and the operation of the internal timer shall not be affected by the operating status of the display device. 5.1.10 The maximum communication distance between the display device and a terminal device should not be less than 1000 m, and the maximum communication distance between the display device and a relay device should not be less than 200 m. 5.1.11 When the display device has a positioning function, the positioning error for continuous positioning type display devices intended for outdoor use only should not be greater than 10 m, and for continuous positioning type display devices intended for indoor use, the positioning error should not be greater than 5 m; the positioning error for anchor positioning type display devices intended for outdoor use only should not be greater than 50 m, and for anchor positioning type display devices intended for indoor use, the positioning error should not be greater than 20 m. 5.1.12 When the display device has a remote measurement function, the maximum effective distance for the display device to complete the checkin function interaction with the remote measurement point should not be greater than 5 m. 5.1.13 The display device shall have complete packaging at the time of product delivery. The packaging shall contain a quality inspection certificate and a Chinese instruction manual.
Contents of GB/T 47438.4-2026
About Us   |    Contact Us   |    Terms of Service   |    Privacy   |    Cancellation & Refund Policy   |    Payment
Tel: +86-10-8572 5655 | Fax: +86-10-8581 9515 | Email: coc@codeofchina.com | QQ: 3680948734
Copyright: Beijing COC Tech Co., Ltd. 2008-2040
 
 
Keywords:
GB/T 47438.4-2026, GB 47438.4-2026, GBT 47438.4-2026, GB/T47438.4-2026, GB/T 47438.4, GB/T47438.4, GB47438.4-2026, GB 47438.4, GB47438.4, GBT47438.4-2026, GBT 47438.4, GBT47438.4